AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 89 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Appendix C.5: ECS and SmartPlate
Table C-5: ECS and SmartPlate
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon
SNVT
Lon Direction
ModBus/Unit
Address
E Valve Addr 29
29
01-Cntl Output
Signal
boilerstate_1
AV:11 data float 1 nvoEcsState29 inc count (9) Output (non-polled) 30004/29
29
02-Setpoint effectsetpt_1
AV:80 data float 2 nvoEcsSetpt29 inc count (9) Output (non-polled) 30006/29
29
03-RmSetpt rmsetpt_1
AV:81 data float 3 nviEcsSetptRq29 inc count (9) Input (non-polling) 40027/29
29
04-Outlet Temp localsuptemp_1
AV:84 data float 4 nvoEcsSupTmp29 inc count (9) Output (non-polled) 30002/29
29
05-FBk Sensor
Temp
localrettemp_1
AV:1 data float 5 nvoEcsRetTmp29 inc count (9) Output (non-polled) 30290/29
29
06-Over Temp
Alarm
unitstat_1
AV:86 data float 6 nvoEcsStat29 inc count (9) Output (non-polled) 30075/29
29
07-Flow Rate flowrate_1
AV:2 data float 7 nvoEcsFlow29 inc count (9) Output (non-polled) 30291/29
E Valve Addr 30
30
01-Cntl Output
Signal
boilerstate_2
AV:12 data float 8 nvoEcsState30 inc count (9) Output (non-polled) 30004/30
30
02-Setpoint effectsetpt_2
AV:3 data float 9 nvoEcsSetpt30 inc count (9) Output (non-polled) 30006/30
30
03-RmSetpt rmsetpt_2
AV:4 data float 10 nviEcsSetptRq30 inc count (9) Input (non-polling) 40027/30
30
04-Outlet Temp localsuptemp_2
AV:5 data float 11 nvoEcsSupTmp30 inc count (9) Output (non-polled) 30002/30
30
05-FBk Sensor
Temp
localrettemp_2
AV:6 data float 12 nvoEcsRetTmp30 inc count (9) Output (non-polled) 30290/30
30
06-Over Temp
Alarm
unitstat_2
AV:7 data float 13 nvoEcsStat30 inc count (9) Output (non-polled) 30075/30
30
07-Flow Rate flowrate_2
AV:8 data float 14 nvoEcsFlow30 inc count (9) Output (non-polled) 30291/30
E Valve Addr 31