Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip Point Name Name
Read
BACnet
N2 Type
N2
Lon SNVT
Lon
Lon Direction
ModBus
Master Addr 247
247
Write Cntrl Val to
BST/WHM
SMD_BAS_IP_Ctrl_[1]
write "1" to
send Value to
WHM
AV:51 Data Float 2 nvoCtrl_2 inc count (9) Input/Output 40051
247 BST/WHM Timeout SMD_BAS_IP_Ctrl_[3]
**Read
Only**,
0=WHM
Present,
1=WHM
Absent
AV:53 Data Float 4 nvoCtrl_4 inc count (9) Input/Output 40053
Read Master Operating Values
247
Mode SMD_BAS_IP_OpVal_[0] AV:100 Data Float 6 nvoOpVal_1 inc count (9) Output (non-polled) 30100
247
Setpoint SMD_BAS_IP_OpVal_[1] AV:101 Data Float 7 nvoOpVal_2 inc count (9) Output (non-polled) 30101
247 Setback Setpt SMD_BAS_IP_OpVal_[2] AV:102 Data Float 8 nvoOpVal_3 inc count (9) Output (non-polled) 30102
247 Setback Start SMD_BAS_IP_OpVal_[3] AV:103 Data Float 9 nvoOpVal_4 inc count (9) Output (non-polled) 30103
247 Setback End SMD_BAS_IP_OpVal_[4]
AV:104 Data Float 10 nvoOpVal_5 inc count (9) Output (non-polled) 30104
247 Auto Master SMD_BAS_IP_OpVal_[5]
AV:105 Data Float 11 nvoOpVal_6 inc count (9) Output (non-polled) 30105
247
Avg Outlet Temp SMD_BAS_IP_OpVal_[6] AV:106 Data Float 12 nvoOpVal_7 inc count (9) Output (non-polled) 30106
247
Units Active SMD_BAS_IP_OpVal_[7] AV:107 Data Float 13 nvoOpVal_8 inc count (9) Output (non-polled) 30107
247 Units Faulted SMD_BAS_IP_OpVal_[8] AV:108 Data Float 14 nvoOpVal_9 inc count (9) Output (non-polled) 30108
247 Master Addr SMD_BAS_IP_OpVal_[9] AV:109 Data Float 15 nvoOpVal_10 inc count (9) Output (non-polled) 30109
247 Header Temp SMD_BAS_IP_OpVal_[10]
AV:110 Data Float 16 nvoOpVal_11 inc count (9) Output (non-polled) 30110
247 Outdoor Temp SMD_BAS_IP_OpVal_[11]
AV:111 Data Float 17 nvoOpVal_12 inc count (9) Output (non-polled) 30111
247
Percent Output SMD_BAS_IP_OpVal_[12] AV:112 Data Float 18 nvoOpVal_13 inc count (9) Output (non-polled) 30112
247
SMD_BAS_IP_OpVal_[13] AV:113 Data Float 19 nvoOpVal_14 inc count (9) Output (non-polled) 30113
247
SMD_BAS_IP_OpVal_[14] AV:114 Data Float 20 nvoOpVal_15 inc count (9) Output (non-polled) 30114