AERCO ProtoNode Gateway
User Manual
Page 18 of 126 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Figure 3-4: Modbus RS-485 Biasing Jumpers on the ProtoNode RER (Left) and
ProtoNode LER (Right)
3.3.3 End of Line Termination Switch for the Modbus RS-485 port on the
ProtoNode
On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each
end.
If the ProtoNode is placed at one of the ends of the trunk, you place the Blue RS-485
End-of- Line terminating jumper to ON position.
On short cabling runs the terminating EOL jumper can remain OFF except when an RS-
232 to RS-485 converter is connected to the HOST (AERCO) port. In that case, put the
terminating jumper in the ON position. The default setting for this blue terminating
jumper is OFF.
Always leave the single Red Jumper in the A position. NEVER move the single
Red jumper.
FIGURE 3-5: Modbus RS-485 End-Of-Line Termination Jumpers on the ProtoNode
RER (Left) and ProtoNode LER (Right)
RS-485 Bias Switch
Leave in A
position
Leave in A
position
Modbus RS-485
EOL Jumper
Modbus RS-485
EOL Jumper