USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment Point Name Name
Read
Only
BACnet
Type:ID
N2 Type N2 ID
Lon SNVT
NAME
Lon SNVT Lon Direction
ModBus/Unit
Address
Blr Addr 6
01-Fire Rate Out boilerstate_6
AV:51 data float 51 nvoBlrState6 inc count (9) Output (non-polled) 30009/6
02-Active Setpoint effectsetpt_6
AV:52 data float 52 nvoEffSetpt6 inc count (9) Output (non-polled) 30017/6
03-Net Remote Setpt setpt_6 AV:53 data float 53 nviSetpt6 inc count (9) Input (non-polling) 40001/6
05-Fire Rate In boilerload_6
AV:55 data float 55 nvoBlrLoad6 inc count (9) Output (non-polled) 30018/6
06-Outlet Temp localsuptemp_6
AV:56 data float 56
nvoLocSupTmp
6
inc count (9) Output (non-polled) 30003/6
07-Display Code dispcode_6
AV:57 data float 57 nvoDispCode6 inc count (9) Output (non-polled) 30001/6
08-Unit Status unitstat_6
AV:58 data float 58 nvoUnitStat6 inc count (9) Output (non-polled) 30002/6
09-Run Cycles runcycles_6
AV:59 data float 59 nvoRunCycles6 51 Output (non-polled) 30012-30013/6
10-Run Hours runhours_6
AV:60 data float 60 nvoRunHours6 51 Output (non-polled) 30014-30015/6
Blr Addr 7
01-Fire Rate Out boilerstate_7
AV:61 data float 61 nvoBlrState7 inc count (9) Output (non-polled) 30009/7
02-Active Setpoint effectsetpt_7
AV:62 data float 62 nvoEffSetpt7 inc count (9) Output (non-polled) 30017/7
03-Net Remote Setpt setpt_7 AV:63 data float 63 nviSetpt7 inc count (9) Input (non-polling) 40001/7
05-Fire Rate In boilerload_7
AV:65 data float 65 nvoBlrLoad7 inc count (9) Output (non-polled) 30018/7
06-Outlet Temp localsuptemp_7
AV:66 data float 66
nvoLocSupTmp
7
inc count (9) Output (non-polled) 30003/7
07-Display Code dispcode_7
AV:67 data float 67 nvoDispCode7 inc count (9) Output (non-polled) 30001/7
08-Unit Status unitstat_7
AV:68 data float 68 nvoUnitStat7 inc count (9) Output (non-polled) 30002/7
09-Run Cycles runcycles_7
AV:69 data float 69 nvoRunCycles7 51 Output (non-polled) 30012-30013/7
10-Run Hours runhours_7
AV:70 data float 70 nvoRunHours7 51 Output (non-polled) 30014-30015/7
C.2.6 - Twelve C-Mores, Six ECS/SP, Four Modulex, and Two ACS/BMS II (Cont.)