GF-129
Pinouts
ProtoNode Pin # Pin assignment
Pin 1 RS-485 +
Pin 2 RS-485 -
Pin 3 RS-485 GND
Pin 4 V +
Pin 5 V -
Pin 6 FRAME GND
4.4 Commissioning the ProtoNode LER on a Lonworks network
Commissioning may only be performed by the LonWorks administrator.
To commission the ProtoNode LER LonWorks port, insert a small screwdriver in the commissioning hole
on the face of the LER’s enclosure to access the Service Pin. See the illustration on the ProtoNode LER as
to which way to toggle the screw driver during commissioning.
4.5 Sending Write Values
The administrator must setup their host management system to write through the gateway to the C-
More, ACS or BMS II three or four times within the timeout value.
AERCO Device Parameter Default Value Range Menu
BMS II
Network Timeout 30 s 5 to 240 s RS-232
C-More
Network Timeout 30 s 5 to 999 s Configuration
ACS
Network Timeout 30 s 5 to 240 s RS-232
Refer to GF-112, GF-124, and GF-131 for more information.
LonWorks Service Pin