AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 VD2:011712
1
GF-129
3.3 Modulex BCM
Figure 7. RS-485 Connection to BCM
3.4 ECS
Figure 8. RS-485 Connection to ECS
Connect ECS terminals HE and HF to XPC Port 1a (Figures 5-7) as follows:
Connect the “HF” terminal to the ProtoNode’s “RS485 +” port
Connect the “HE” terminal to the ProtoNode’s “RS485 -” port
TERMINATE SHIELD
TO SIGNAL GROUND
TIE TOGETHER WITH
SHIELDS OF OTHER
UNITS AND
FLOAT AT END OF
LINE (INSULATE)
TERMINATE SHIELD
TO SIGNAL GROUND
TIE TOGETHER WITH
SHIELDS OF OTHER
UNITS AND
FLOAT AT END OF
LINE (INSULATE)