E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 10: E8, BCM, AND BMM FAULT CODES
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 105 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
10.2.4 BMM Fault Code Table
The table below lists the fault codes and troubleshooting tips associated with the BMM.
Table 10-4: BMM Fault Codes
1
High Limit (STB)
Thermostat
activated
All burners
turned OFF and
Pump ON at
maximum speed.
Check FlowSensor
thermal connection to
boiler.
reset switch
when
temperature
2
Low Gas
Pressure
All burners
turned OFF.
Check gas pressure or
gas pressure switch.
when gas
pressure switch
4
detected at
Burner control
lockout.
Check flame rod or
combustion.
reset switch or
5
Flame loss during
run.
Ignition retry.
Check combustion and
wiring.
reset switch or
6
temperature.
FlowSensor
temperature >
All burners
turned OFF and
Pump ON at
maximum speed.
Check Flow Sensor or
system pump.
AUTOMATIC -
when
FlowSensor <
176°F.
10
Internal Failure
Contact Factory for new
BCM.
MANUAL - cycle
the power.
11
Flame signal
detected before
ignition.
Ignition is
inhibited.
Disconnect flame rod wire
from BMM. If problem
goes away change flame
rod and/or wire. If problem
does not go away change
MANUAL - push
reset switch or
cycle power.
12
FlowSensor fault.
Check flow sensor or
wiring.
AUTOMATIC
13
Aux Sensor fault
operate from the
FlowSensor
without the
Check aux sensor or
wiring.
AUTOMATIC